Basic Operation

5-4 Selecting the Operation Command

The following description provides information on how to input operation
commands to start or stop the Inverter or change the direction of rotation of
the Inverter.
Two types of command input methods are available. Select either one of
them according to the application.
Selecting the Operation Mode (n02)
Select the method of operation mode input to start or stop the Inverter.
The following method is enabled in remote mode only. The command can be input
through key sequences on the Digital Operator.
Operation Command Selection
n02
Setting
0, 1
range
Set Values
Value
0
The RUN and STOP/RESET Keys of the Digital Operator are enabled.
1
Multi-function input in 2- or 3-wire sequence through the control circuit
terminals is enabled.
Selecting the STOP/RESET Key Function (n06)
When parameter n02 is set to 1, set whether or not to use the STOP/RESET Key of the
Digital Operator to stop the Inverter in remote mode. The STOP/RESET Key is always
enabled in local mode regardless of the setting in n02.
STOP Key Function Selection
n06
Setting
0, 1
range
Set Values
Value
0
The STOP/RESET Key of the Digital Operator is enabled.
1
The STOP/RESET Key of the Digital Operator is disabled. This setting is
available only when the Digital Operator is selected for operation command
input.
Unit of
1
setting
Description
Unit of
1
setting
Description
Chapter 5
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0