Configure switch configuration
 Make sure that the power is turned OFF before installing/removing any boards or
connecting/disconnecting any cables. Working with the power ON is extremely
hazardous and may result in electrical shock and/or malfunction of equipment.
WARNING
Set the node address of the device using the address configuration switch of the
PROFIBUS-DP slave board. Set network termination ON or OFF with the terminator
switch.
1.
NOTE
Generally, a node address from 0 to 125 is available for the PROFIBUS-DP device.
However, this Robot system supports node addresses from 0 to 99.
2.
Wiring
PROFIBUS-DP connector is standard 9-pins D-sub connector.
Terminal name for each pin
NOTE
Prepare the cable for PROFIBUS-DP sold in the market as a communication cable.
Install terminating resistors at both ends of the network.
A terminating resistor is installed in the PROFIBUS-DP slave board. Turn the terminating
resistor ON or OFF using the terminator switch on the front panel.
RC700 / RC90 Option Fieldbus I/O Rev.12
Set the node address of the PROFIBUS-DP slave board using the address
configuration switch. Make sure that the node address is different from the other
devices in the network. Switch on the "×10" side is for tenths digit address
configuration. Switch on the "×1" side is for units digit address configuration.
Generally, node addresses are
recommended to be configured
as shown in the table.
Turn the network termination ON or OFF using the terminator switch.
Terminal No
Terminal Name
Case
Shield
1
2
3
B line
4
RTS
5
GND BUS
6
+5V BUS
7
8
A line
9
Node address
0
1
2
3-99 (-125)
NC
NC
NC
NC
2. Installation
Device Name
Service unit such as PG/PC
Operation panel such as HMI
Master station
DP slave station
87