Epson RC700 Manual page 134

Robot controller fieldbus i/o
Hide thumbs Also See for RC700:
Table of Contents

Advertisement

2. Installation
How to change the set value on the master side
Set "0x0000" of UINT below.
Describe the procedures to set on applicomIO 4.2 Console application.
(1) Connect the fieldbus master and the slave.
(2) Select [Network]-[Online Action] on the menu of the [applicomIO Console]
(3) The [Outline Action] dialog is displayed. Select the [Explicit Message] tab.
(4) Click the <Send to Device> button.
(5) Confirm that the "CIP Status: 0x0. Success" is displaye on the [Status].
124
TCP/IP Interface Object (F5h) class - Instance #1 - Attribute#13
- Encapsulation Inactivity Timeout
application.
Set as follows:
Address
IP Address
:
Class
:
Instance
:
Attribute
:
Service
Name
:
Data
:
Now, changing the setting is complete.
IP address of the fieldbus EtherNet/IP slave
0x000000F5
1
13
Set_Attribute_Single
0000
RC700 / RC90 Option Fieldbus I/O Rev.12