Epson RC700 Manual page 256

Robot controller fieldbus i/o
Hide thumbs Also See for RC700:
Table of Contents

Advertisement

4. Troubleshooting (PROFIBUS DP)
♦ Process Flowchart
Check for cable laying.
Check that
terminating resistors
are connected.
Normal
Turn OFF all units.
Measure resistance
with tester.
100 to 120 Ω
Normal
See 4.2.3.2.
246
Problem exists.
(Add terminating resistors.)
Out of 100 to 120 Ω (Error)
Resistance: over 120 Ω
Yes
Remove one terminating
resistor on either side.
Approx.
Measure
220
resistance at
connectors
with tester.
Other
Find the trouble point.
(1) Unconnected or loose connector
(2) Cable disconnection, etc.
No
Resistance: under 100 Ω
10 to 100 Ω
Check for connection
of terminating resistors.
(1) Three or more
terminating resistors
(2) Wrong terminating
resistors, etc.
RC700 / RC90 Option Fieldbus I/O Rev.12
Under 10 Ω
Check for short
circuit between
signal wires.
Short circuit
between signal
wires

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rc90

Table of Contents