Group 99: Start-up Data

The Start-up Data parameters are a special set of parameters for setting up the ACS 400 and for
entering motor information.
Code Description
9901 LANGUAGE
Language selection for the ACS-PAN-A control panel.
0 =
ENGLISH
1 =
(
ENGLISH
AM
2 =
GERMAN
9902 APPLIC MACRO
Application macro selection. This parameter is used to select the Application Macro which will configure the
ACS 400 for a particular application. Refer to "Application Macros" on page 53, for a list and description of
available Application Macros.
0 =
FACTORY
1 =
ABB STANDARD
9905 MOTOR NOM VOLT
Nominal motor voltage from motor rating plate. This parameter sets the maximum output voltage supplied to
the motor by the ACS 400.
MOTOR NOM VOLT
voltage.
See Figure 25.
9906 MOTOR NOM CURR
Nominal motor current from motor nameplate. The allowed range is 0.5 · I
9907 MOTOR NOM FREQ
Nominal motor frequency from motor nameplate (field weakening point).
See Figure 25.
9908 MOTOR NOM SPEED
Nominal motor speed from motor nameplate.
9909 MOTOR NOM POWER
Nominal motor power from motor nameplate.
9910 MOTOR COS PHI (MOTOR POWER FACTOR)
Nominal motor cos phi from motor nameplate.
Figure 25 Output voltage as a function of output frequency.
ACS 400 User's Manual
3 =
ITALIAN
)
4 =
SPANISH
5 =
PORTUGUESE
2 = 3-
WIRE
3 =
ALTERNATE
MOTOR NOM FREQ
. The ACS 400 cannot supply the motor with a voltage greater than the input supply
Output voltage
MOTOR NOM VOLT
http://nicontrols.com
6 =
9 =
DUTCH
7 =
10 =
FRENCH
8 =
11 =
DANISH
4 =
6 =
MOTOR POT
5 =
/
7 =
HAND
AUTO
sets the frequency at which output voltage is equal to the
MOTOR NOM FREQ
12 = (reserved)
FINNISH
SWEDISH
RUSSIAN
8 =
PID CONTROL
PFC CONTROL
PREMAGN
... 1.5 · I
of ACS 400.
N
N
Output frequency
73