Auxiliary Circuit Power Consumption; Efficiency; Energy Efficiency Data (Ecodesign); Protection Classes For Module - ABB ACH580-01 Hardware Manual

Table of Contents

Advertisement

298 Technical data

Auxiliary circuit power consumption

Efficiency

Energy efficiency data (ecodesign)

Energy efficiency data according to IEC-61800-9-2 is available from the ecodesign tool
(https://ecodesign.drivesmotors.abb.com).

Protection classes for module

Degrees of protection
(IEC/EN 60529)
Enclosure types (UL
50/50E)
Overvoltage category
(IEC/EN 60664-1)
Protective class
(IEC/EN 61800-5-1)
Maximum external power supply:
Frames R1...R5: 25 W, 1.04 A at 24 V AC/DC (with option modules
CMOD-01, CMOD-02)
Frames R6...R9: 36 W, 1.50 A at 24 V AC/DC (as standard, terminals
40...41)
Approximately 98% at nominal power level. The efficiency is not
calculated according to IEC 61800-9-2.
IP21 (standard)
IP20 (option +P940, +P944)
IP55 (option +B056)
UL Type 1
UL Open Type(option +P940, +P944)
UL Type 12 (option +B056)
III
I

Advertisement

Table of Contents
loading

Table of Contents