Parameter Description

3.5 Parameters 3-** Reference/Ramps

3.5.1 3-0* Reference Limits
3-02 Minimum Reference
Range:
Size
[ -999999.999 - par.
related
3-03 ReferenceFeed-
*
backUnit]
3-03 Maximum Reference
Range:
Size
[
par. 3-02 -
related
999999.999
*
ReferenceFeed-
backUnit]
3-04 Reference Function
Option:
Function:
[0]
Sum
Sums both external and preset reference
*
sources.
[1]
External/Preset Use either the preset or the external
reference source.
Shift between external and preset via a
command or a digital input.
3.5.2 3-1* References
Select the preset reference(s). Select Preset ref. bit 0/1/2
[16], [17] or [18] for the corresponding digital inputs in
parameter group 5-1*.
3-10 Preset Reference
Array [8]
Range:
Function:
0.00
[-100.00 -
Enter up to eight different preset
%
100.00 %]
references (0-7) in this parameter, using
*
array programming. The preset reference
is stated as a percentage of the value
Ref
(3-03 Maximum Reference). When
MAX
using preset references, select Preset ref.
bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in parameter
group 5-1* Digital Inputs.
®
VLT
AQUA Drive Programming Guide
Function:
Enter the desired minimum
value for the remote reference.
The Minimum Reference value
and unit matches the configu-
ration choice made in
1-00 Configuration Mode and
20-12 Reference/Feedback Unit,
respectively.
Function:
Enter the maximum acceptable
value for the remote reference.
The Maximum Reference value
and unit matches the configu-
ration choice made in
1-00 Configuration Mode and
20-12 Reference/Feedback Unit,
respectively.
®
MG20O602 - VLT
is a registered Danfoss trademark
P3-03
P3-02
0
50
Illustration 3.12
12 (+24V)
Preset
76543210
29
[P 5-13=Preset ref. bit 0]
10101010
11001100
32
[P 5-14=Preset ref. bit 1]
33
11110000
[P 5-15=Preset ref. bit 2]
Illustration 3.13
3-11 Jog Speed [Hz]
Range:
Function:
Size related
[ 0.0 - par.
The jog speed is a fixed output
*
4-14 Hz]
speed at which the frequency
converter is running when the jog
function is activated.
See also 3-80 Jog Ramp Time.