7 ONLINE MODULE CHANGE
7.3 Online Module Change Procedure
7.3.1 When GX Configurator-TC is used for the initial setting
7 - 4
This section describes two online module change procedures: configuring the initial
settings using GX Configurator-TC and configuring the initial settings using a sequence
program.
(1) Stopping operation
(a)
Turn off the following output signals to stop module operation.
Device No.
Yn1
Yn8
Yn9
YnB
POINT
Control may not stop even when Setting/operation mode command (Yn1) is turned
off.
To stop control without fail, set 0 (Stop) in PID continuation flag (buffer memory
address: 169) and turn off Setting/operation mode command (Yn1).
The stop status can be checked with Setting/operation mode status (Xn1) (off:
Stop).
Signal name
Setting/operation mode command
FeRAM backup start command
Default setting registration start command
Setting change command
MELSEC-Q
7 - 4