7
ONLINE MODULE CHANGE
7.3.1
(1) Conversion disable
(2) Dismounting of module
.
7.3 Online Module Change Procedure
7
- 5

7.3.1 When industrial shipment setting is used and initial setting was made with GX Configurator-AD

When industrial shipment setting is used and initial setting was
made with GX Configurator-AD
(a) Set the A/D conversion enable/disable setting (Un\G0) for all channel conversion
disable and turn operating condition setting request (Y9) from OFF to ON to stop
conversion.
After confirming that conversion has stopped with the A/D conversion completion
flag (Un\G10), turn off Operation Condition Setting Request (Y9).
(The window shows the setting example of the Q68AD-G.)
(a) After choosing [Diagnosis] - [Online module change] on GX Developer to enter the
"Online module change" mode, double-click the module to be changed online to
display the "Online module change" window.