Control of Extended Functions without encoder via terminals (only CU310-2)

The table below shows the response times
until the response is initiated.
Extension of the response times for SLS without encoder or SDI without encoder under
certain circumstances
If the safety functions SLS without encoder or SDI without encoder are already selected
when the gating pulses for the Power Module are enabled, then during the starting phase, it
is absolutely imperative that you take into account that the response times – when limit
values are violated and for system errors – are extended by the time value set in parameter
p9586
After the time interval set in p9586, the standard response times apply (see table above).
Table 8- 8
Response times for control of the Extended Functions without encoder via terminals (only CU310-2)
Function
STO
SBC
SS1
(speed controlled/time and acceleration controlled),
SS1E (time controlled)
SBR or SAM (limit value violation until STO active)
SLS speed limit violated
SSM
SDI (limit value violation until
braking is initiated)
The specified response times are valid for Extended Functions with and without selection!
1)
Start phase: This describes the behavior after switching on (ON command with previously deleted pulses).
2)
Standard: This behavior applies when the pulses have already been enabled.
There is a different behavior because, with the aid of p9586, the encoderless actual value acquisition after pulse enable
can only be activated after a delay.
For t_E, the following applies:
3)
p10017 = 0
t_E = 2 · p0799
p10017 ≠ 0
t_E = p10017 + p0799 + 1 ms
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
CAUTION
with respect to the standard values (see table above).
2)
Standard
3)
2)
Start phase
2)
Standard
2)
Start phase
2)
from the occurrence of a signal at the terminals
1)
Drive system has no fault
3,5 · p9500 + r9780 + t_E
3,5 · p9500 + 2 · r9780 + t_E
3,5 · p9500 + 2 ms + t_E
3)
3 · p9500 + r9780 + p9587 +
4 ms
3 · p9500 + p9587 + 6 ms
3 · p9500 + p9586
+ p9578 + 6
2)
ms
4 · p9500 + p9587 + 4 ms
2,5 · p9500 + p9587 + 6 ms
2,5 · p9500 + p9587 + p9586
6 ms
System features
8.4 Response times
Worst case for
A fault is present
4 · p9500 + 2 · r9780 + t_E
3)
4 · p9500 + 9 · r9780 + t_E
3)
4 · p9500 + 2 ms + t_E
3,5 · p9500 + r9780 + p9587 +
32 ms
4,5 · p9500 + r9780 + p9578 +
32 ms
4,5 · p9500 + r9780 + p9586
p9578 + 32 ms
4,5 · p9500 + p9587 + 32 ms
4 · p9500 + r9780 + p9587 +
32 ms
+
4 · p9500 + r9780 + p9587 +
2)
p9586
+ 32 ms
2)
3)
3)
3)
+
2)
365