Control Of Extended Functions Without Encoder Via Tm54F (Cu310-2 And Cu320-2) - Siemens SINAMICS S120 Function Manual

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System features
8.4 Response times
8.4.9
Control of Extended Functions without encoder via TM54F (CU310-2 and
CU320-2)
The table below shows the response times
until the response is initiated.
Extension of the response times for SLS without encoder or SDI without encoder under
certain circumstances
If the safety functions SLS without encoder or SDI without encoder are already selected
when the gating pulses for the Power Module are enabled, then during the starting phase, it
is absolutely imperative that you take into account that the response times – when limit
values are violated and for system errors – are extended by the time value set in parameter
p9586
After the time interval set in parameter p9586, the standard response times apply (see table
above).
Table 8- 9
Response times for control via TM54F
Function
STO
SBC
SS1
(speed controlled/time and acceleration controlled),
SS1E (time controlled)
SBR or SAM (limit value violation until STO active)
SLS speed limit violated
SSM
SDI (limit value violation until brak-
ing is initiated)
The specified response times are valid for Extended Functions with and without selection!
1)
Start phase: This describes the behavior after switching on (ON command with previously deleted pulses).
2)
Standard: This behavior applies when the pulses have already been enabled.
There is a different behavior because, with the aid of p9586, the encoderless actual value acquisition after pulse enable
can only be activated after a delay.
For CU310-2, use the parameter p10017 of the drive object "TM54F_xx" to calculate the response time, not that of the
3)
control unit.
366
CAUTION
with respect to the standard values (see table above).
2)
Standard
3)
2)
Start phase
2)
Standard
2)
Start phase
2)
from the occurrence of a signal at the terminals
1)
Drive system has no fault
3,5 · p9500 + r9780 + p10017
+ 1 ms
3,5 · p9500 + 2 · r9780 +
p10017
+ 1 ms
3)
3,5 · p9500 + p10017
+ 3 ms
3)
3 · p9500 + +r9780 + p9587 + 4
ms
3 · p9500 + p9587 + 6 ms
3 · p9500 + p9587 + p9586
6 ms
4 · p9500 + p9587 + 4 ms
2,5 · p9500 + p9587 + 6 ms
2,5 · p9500 + p9587 + p9586
+ 6 ms
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Worst case for
A fault is present
4 · p9500 + 2 · r9780 + p10017
3)
+ 1 ms
4 · p9500 + 6 · r9780 + p10017
+ 1 ms
4 · p9500 + p10017
3,5 · p9500 + r9780 + p9587 +
32 ms
4,5 · p9500 + r9780 + p9587 +
32 ms
+
4,5 · p9500 + r9780 + p9587 +
2)
p9586
+ 32 ms
2)
4,5 · p9500 + p9587 + 32 ms
4 · p9500 + r9780 + p9587 +
32 ms
4 · p9500 + r9780 + p9587 +
2)
p9586
+ 32 ms
2)
3)
3)
+ 3 ms
3)
Safety Integrated

Hide quick links: