Status display
The following elements show the current status of the forced checking procedure:
● Time remaining:
Shows the time remaining until the forced checking procedure and the test of the safety
shutdown paths are performed (r9660 for the Basic Functions, r9765 for the Extended
Functions).
● Test stop required:
Shows that a forced checking procedure (test stop) must be performed on the drive.
Evaluate alarm A01699 in your higher-level controller, for example, by connecting
r9773.31 or r9723.0 to a digital output or a bit in the fieldbus status word (r9773.31 for the
Basic Functions, r9723.0 for the Extended/Advanced Functions).
6.8.4.4

Function status of the Safety Integrated settings

The "Function Status" screen form displays a list of all Safety Integrated functions on the left.
Figure 6-12
All Safety Integrated functions activated in Startdrive are identified by a green LED.
In addition, the most important information of the selected Safety Integrated functions is
displayed.
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
"Drive axis > Parameter > Safety Integrated > Function status"
Example: Safety Integrated Function status
Commissioning
6.8 Commissioning: Basic procedure