Description of Safety Integrated functions
4.1 Safety Integrated basic functions
4.1.1.1

Safe Torque Off (STO) for SINAMICS HLA

For the HLA module, safe torque off (STO) corresponds to shutting off a safety-relevant
shutoff valve.
Special features of STO for HLA
● The shutoff valve controls the infeed to the hydraulic circuit. The shutoff valve is
controlled via an F-DO of SINAMICS HLA.
● For Safety Integrated Functions, it is absolutely necessary that a shutoff valve is
connected with the associated feedback signals.
● You configure the feedback signal contacts of the shutoff valve using parameter p9626.
● You can take into account the response times of the feedback signals using parameter
p9625.
● The shutoff valve is safely closed by selecting STO. If the shutoff valve signals a safe
state via the feedback signal(s), the "STO active/Power removed" state is displayed, and
is output at the configured safety-related output (PROFIsafe feedback signal telegram, F-
DO on TM54F).
Figure 4-1
● F-DO is dynamized each time that STO is selected/deselected: "Diag DO+" and "Diag
DO-" are checked when switching F-DO+ and F-DO-.
● This makes it unnecessary to select forced checking procedure (test stop) explicitly.
● If an error occurs in the forced checking procedure (test stop), the converter will issue
fault F01632 or F30632.
74
Interconnecting the shutoff valve (for an axis)
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Safety Integrated