Description of Safety Integrated functions
4.3 Safety Integrated Advanced Functions
Executing a forced checking procedure (test stop)
Forced checking procedure (test stop) can be executed at the following points in time:
1. Forced checking procedure (test stop) can be initiated application-specifically and can
therefore be executed at a time that suits application requirements.
This functionality is implemented by means of a single-channel parameter p9705, which
can be wired via BICO either to an input terminal on the drive unit (Control Unit) - or to a
bit of any arbitrary PZD.
In addition, it is possible to select the test stop via the Safety Control Channel (see
Chapter "Safety Info Channel and Safety Control Channel (Page 251)").
– p9559 SI Motion Forced checking procedure timer (Control Unit)
– p9705 BI: SI Motion test stop signal source
– r9723.0 CO/BO: SI Motion diagnostics signals integrated in the drive
If the test stop is executed as described, the action does not require a POWER ON. The
acknowledgment is set by canceling the test stop request.
2. Forced checking procedure (test stop) can be automatically executed at POWER ON.
– To perform an automatic test stop of the Safety Integrated Extended/Advanced
– To perform automatic forced checking procedure (test stop) of the F-DI and F-DO of
– Even if you have parameterized forced checking procedure (test stop) for POWER
– If the automatically initiated function cannot be correctly completed as a result of a
– After the forced checking procedure (test stop) has been performed successfully, the
– Timer p9559 is reset as a result of the automatic forced checking procedure (test
– The automatic forced checking procedure (test stop) for POWER ON does not
In all cases, the scope of forced checking procedure (test stop) function is identical.
196
Functions as well as an automatic test of the F-DO for the CU310-2, set p9507.6 = 1.
When testing the F-DO of the CU310-2, you must parameterize p10042 and activate
the test in p10046.
Note
Automatic forced checking procedure (test stop) and SBT
Automatic forced checking procedure (test stop) of the Safety Integrated
Extended/Advanced Functions is possible together with the "Brake test for test stop
selection" function (p10203 = 2).
the TM54F, set p10048 = 1.
ON, you can still initiate a test stop at any time through the application.
problem (e.g. communication failure), the function will be automatically restarted after
the problem has been resolved.
converter goes into the "Ready" state.
stop).
influence the Safety Integrated Functions.
Function Manual, 12/2018, 6SL3097-5AR00-0BP1