Commissioning
6.6 Safety Integrated and ESR
6.6
Safety Integrated and ESR
The following table lists the options that SINAMICS Safety Integrated offers for ESR. There
are 3 variants in which the converter triggers ESR:
1. STOP E
Internal response to a limit value violation + SLS, SDI, SLP, SLA with subsequent
response
2. STOP F
Defect in a monitoring channel + programmed subsequent response with STOP B →
STOP A
3. Communication breakdown
Cable, CPU STOP, ...
Variant
ESR inte-
1
grated in the
drive ("inter-
nal" ESR)
2
3
274
Basic Functions
STOP E: NOT POSSIBLE → SS1 immedi-
•
ately responds with STOP B
STOP F (defect in a monitoring channel +
•
programmed subsequent response with
STOP B → STOP A)
E. g. for a discrepancy at the input termi-
•
nals
Basic Functions, set r9734.14
•
p0890[4] = r9734.14
•
Communication breakdown: NOT
•
POSSIBLE
Extended/Advanced Functions
STOP E (internal response to a limit value
•
violation + SLS, SDI, SLP, SLA with sub-
sequent response)
Is initiated when a limit value is violated,
•
for example
For these functions, the following value is
•
monitored:
p0890[1] = r9721.15 (Safety Integrated
STOP E)
STOP F (defect in a monitoring channel +
•
programmed subsequent response with
STOP B → STOP A)
In the transition time from STOP F to
•
STOP B, you can request an ESR.
p0890[2] = r9723.1 (Safety Integrated
•
STOP F)
Communication error (cable, CPU STOP,
•
...)
During the "Delay for bus failure" (p9580)
•
from STOP F to STOP B, you can request
an ESR.
p0890[3] = r9723.2 (Safety Integrated
•
communication failure)
NOTE: As p9580 delays the initiation of
•
STO, you must explicitly select a safety
function with delay. For this function, pa-
rameterize a STOP with delayed STO
when the bus fails (e.g. p9563 for SLS).
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Safety Integrated