Parameterization of the grouping
The grouping must be configured (DI on Control Unit) and wired (EP terminals) identically in
both monitoring channels.
Note
Response of STO for grouping
If a fault in a drive results in a "Safe Torque Off" (STO), this does not automatically mean
that the other drives in the same group also switch to "Safe Torque Off" (STO).
The assignment is checked during the test for the switch-off signal paths. The operator
selects "Safe Torque Off" for each group. The check is drive-specific.
Example: Terminal groups
It must be possible to select/deselect "Safe Torque Off" separately for group 1 (drives 1 and
2) and group 2 (drives 3 and 4). For this purpose, the same grouping for "Safe Torque Off"
must be realized both for the Control Unit and the Motor Modules.
Figure 5-2
Example: Grouping terminals with Motor Modules Booksize and CU320-2
Information on the parallel connection of chassis type Motor Modules
When chassis type Motor Modules are connected in parallel, a safe AND element is created
on the parallel drive object. The number of indexes in p9620 corresponds to the number of
parallel chassis components in p0120.
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
5.2 Control signals by way of terminals on the Control Unit and Motor / Power Module
Control of the safety functions