Commissioning Cu310-2; Basic Sequence Of Commissioning - Siemens SINAMICS S120 Function Manual

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

6.9

Commissioning CU310-2

6.9.1

Basic sequence of commissioning

The following preconditions must be met to configure Safety Integrated on the CU310-2:
● Concluded initial commissioning of all drives
● Connect the sensors to the F-DIs and an actuator to the F-DO (if used)
Configuration sequence
1. Configuring Safety functions of the CU310-2
2. Configuring inputs (if used)
3. Configuring outputs (if used)
4. Copy parameters to the 2nd drive object
5. Change the safety password
6. Activate the configuration by selecting "Activate settings"
7. Save the entire project to Startdrive
8. Save the project in the drive by selecting "Copy RAM to ROM"
9. Execute POWER ON
10.Acceptance test
Note
Commissioning CU310-2
• The CU310-2 is still not available in Startdrive.
• You can find information on commissioning with STARTER in older editions of this
manual.
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
Commissioning
6.9 Commissioning CU310-2
305