Control via F-DI (TM54F or onboard terminals)
1. Using parameters p10009, parameterize an F-DI, with which you can select/deselect the
internal retract logic function.
2. Parameterize two F-DIs for the selection/deselection of the SDI positive and SDI negative
functions in an independent acceptance test.
3. Proceed as follows for an SLP limit violation:
– Switch the signal at the F-DI "retract" from 0 to 1 (the signal edge is evaluated). The
– Safe acknowledgment of the limit violation
– Move the drive into the range that has been enabled using the appropriate setpoint
– Switch the signal at the F-DI "retract" from 1 to 0 (the signal edge is evaluated): As a
Figure 4-29
Time behavior of SLP and retraction
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
retract function is active at all drives that are safely referenced and where presently a
limit value has been violated. When the retract function is active, SLP is inactive and
depending on which limit which has been violated, either SDI positive or SDI negative
is selected.
inputs.
consequence, SDI is again deselected and SLP is active again.
Description of Safety Integrated functions