8.4.10
Control of Advanced Functions with encoder via PROFIsafe (CU310-2 and
CU320-2)
The following table lists the response times
Control Unit up to initiating the particular response.
Table 8- 10
Response times when controlling via PROFIsafe
Function
SLP (limit value violation until a response is initiated)
SCA: Time between violation of a cam start or end
position and output of the feedback message in
S_ZSW_CAM1
SP
with isochronous PROFIsafe telegram
4)
The specified response times involve internal SINAMICS response times. Program run times in the F-host and the
1)
transmission time via PROFIBUS or PROFINET are not taken into account. When calculating the response times be-
tween the F-CPU and the converter, you must take into account that faults in the communication can result in a safety
function only being selected after the PROFIsafe monitoring time (F_WD_Time) has expired. The PROFIsafe monitoring
time (F_WD_Time) must also be included in the calculation when an error occurs.
t_ACT:
2)
For isochronous communication
For non-isochronous
communication
SP: The data corresponds to the times between acquisition of the safe position and transfer of the safe position via
4)
PROFIsafe.
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
1)
Drive system has no fault
1.5 · p9500 + 2 ms
3.5 · p9500
3 · p9500
t_K = To (for To, see parameter r2064[4])
t_K = 4 ms
(for modules, on which p2048 or p8848
t_K = value from p2048 or p8848
(for modules on which p2048 or p8848
from receiving the PROFIsafe telegram at the
Worst case for
A fault is present
3 · p9500 + 2 ms + t_ACT
4 · p9500 + t_ACT
3 · p9500 + t_ACT
does not exist)
7)
7)
exists)
7)
System features
8.4 Response times
2)
2)
2)
367