Siemens SINAMICS S120 Function Manual page 291

Safety integrated
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4. Call "STO/SS1/SBC" again.
5. To configure the "SS1" function, set the delay time until the start of "STO" in the "Safe
stop 1 delay time" field.
6. Then connect the signal source r9773.1 for the "STO active in the drive" function.
7. Click the
Figure 6-7
8. Click "Save project" in the toolbar to save the changes in the project.
9. Accept these settings in the drive: Chapter "Accepting the settings in the drive
(Page 286)"
Result
You have configured the Safety Integrated Basic Functions.
Safety Integrated
Function Manual, 12/2018, 6SL3097-5AR00-0BP1
button (brake control) to configure the "SBC" function.
Example: Brake control without motor holding brake
Commissioning
6.8 Commissioning: Basic procedure
289