SECTION 6 - JLG CONTROL SYSTEM

Tilt Sensor Calibration

Refer to Figure 6-2., Tilt Sensor Location.
DO NOT CALIBRATE THE TILT SENSOR EXCEPT ON A LEVEL SURFACE.
1. Place the machine on a firm, level surface.
2. Using the analyzer, go to Service Access level. Refer to
Changing the Access Level of the Hand Held Analyzer in
this section.
3. Using the arrow keys, navigate to Calibrations Menu as
shown below and press ENTER
6-6
4. Using the arrow keys, navigate to the Tilt Sensor calibra-
.
tion as shown below and press ENTER
the screen will then read:
.
3121671