AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
If any unclear, please see FC parameter group multi steps time order fig.
F1.24
Emergency stop DEC time
Used to set the DEC time of emergency stop; it is the same as the definition of ACC/DEC time.
Emergency stop can be take effect by emergency stop terminal; details refer to [F2.00-F2.07]. When terminal control
two line run, whether carry out the original run order is decided by [F2.13] LED "00" digit. Details refer to [F2.13].
When multifunction terminal is set as emergency stop, refer to detail [F2.29-F2.31].
F1.25
FWD&REV dead area time
F1.26
Min output frequency
FWD&REV dead area time: Waiting time at 0.0Hz when switch between FWD/REV. It sets for equipment with machine
dead area when big inertia load and change direction.
Note: [F1.25] is valid only for the FWD&REV dead area of the speed control mode, the FWD&REV dead area of
torque control mode is determined by [F7.12].
Min output frequency: If lower than this frequency, inverter output 0.00Hz
F1.27
0 speed hold torque
Set output torque at 0 speed. If the torque setting is too big or the duration is too long during the time of use, the cooling
of motors should be noticed.
F1.28
0 speed hold torque time
Set output torque keep time at 0 speed. Count from 0Hz, stop output when arriving this set time. Valid count value
range is 0-5999.9s. Frequency inverter counts as setting when it is within valid range and stop 0 speed hold torque
when time finished.
If set as 6000.0s, frequency inverter will not count, default as 0 speed hold torque always valid and only stop when stop
or give running frequency not 0.
Suitable 0 speed hold torque time setting can save energy effectively and protect motor.
Note: o speed torque hold is only valid when F0.00=0, F0.00=1orF0.00=4;Please pay attention to motor
temperature rise when 0 speed hold torque time is too long or 0 speed hold torque is too big. If temperature
rises too high, it needs add equipment to improve motor radiation.
Setting range: 0.01-650.00s
Setting range: 0.0-120.0s
Setting range: 0.00-60.00Hz
Setting range: 0.0-150.0%
Setting range:0.0-6000.0s
91
FUNCTION PARAMETER SPECIFICATION
Factory default: 10.00s
Factory default: 0.0s
Factory default: 0.50Hz
Factory default: model setting
Factory default: 0.0s