AC100 HIGH-PERFORMANCE VC INVERTER MANUAL

8.5 Keyboard and Display Parameters

Parameter and key lock
F4.00
selections
0: Unlock Parameter and keyboard lock function invalid.
1: Parameter lock: Lock all function parameter settings, can't modify (except theF0.08). Keyboard can't log in the
parameter setting. All buttons in the keypad are unlocked.
2: Parameter and key lock (except FWD/STOP/JOG) Lock all parameter settings, can't modify. And lock all keys on
keyboard except FWD/STOP/JOG.
3: All parameter and key lock: Lock all parameter settings, can't modify. And lock all keys on keyboard except PRG.
Note:
1. Double lines keypad unlock method: Press "PRG" and 1
and move to 2
line, then enter password (F4.01-user password) and press "SET".
nd
2. Single line keypad unlock method: Press "PRG" and show "CodE". Press "SET" then enter password
(F4.01-user password) and press "SET" again and will be clear!
3. User password is a parameter which purpose is to protect the inverter from tampering at will. In order to
avoid bring inconvenience, please keep it confidential!
F4.01
User password
It is used to set user password. When [F4.00] is (not 0) lock state, password input is needed to unlock. Factory default
is 0.
F4.02
REV/JOG selections
Used to select the REV/JOG function of the keyboard
0: REV When keyboard control, press this button, inverter reverse run. Key REV/JOG not light.
1: JOG When keyboard control, press this button, inverter JOG. Key REV/JOG light.
F4.03
STOP key function range
LED "0"digit: terminal control selection
0: invalid to terminal order: When terminal given signal, STOP key can't control to stop.
1: valid to terminal order: When terminal given signal, STOP key can control to stop.
LED"00"digit: communication control selection
0: invalid to communication order: When terminal given signal, STOP key can't control to stop.
1: valid to communication order: When terminal given signal, STOP key can control to stop.
LED "000" digit: reserved
LED "0000" digit: reserved
Note: When valid to terminal order or communication order, inverter is in stop lock state after press STOP. If
inverter needs to restart, stop order needs to be given by selected order channel to unlock stop state firstly.
F4.04
UP/DOWN key modification selections
LED "0" digit: keyboard UN/DOWN key modify selection
0: Invalid UP/DOWN key can't modify parameters.
1: Modify frequency setting by key board numbers (F0.08) UP/DOWN key can modify settings of [F0.08].
Setting range: 0-3
line show "CodE". And use the "UP"-"DOWN" key
st
Setting range: 0-9999
Setting range: 0-1
Setting range: 0000-0011
Setting range: 0000-0014
114
FUNCTION PARAMETER SPECIFICATION
Factory default: 0
Factory default: 0
Factory default: 0
Factory default: 0000
Factory default: 0011