AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
2: Reserved
3: Modify PID give setting by key board numbers (Fb.01) UP/DOWN key can modify settings of [Fb.01].
4: Reserved
LED "00" digit: keyboard UN/DOWN key store selection
0: No save after power down
1: Save after power down
It is used to select whether to save the parameter modified by UP/DOWN key when power cut.
LED "000" digit: reserved
LED "0000" digit: reserved
F4.05
Function parameter copy
0: No operation
1: Send machine parameters to keyboard and save
store in the inverter.
2: Send parameters saved by keyboard to machine
Note:
1. Keyboard will not send stored parameters to inverter when inverter is running or in fault state or no data
stored in keyboard.
2. When sending data to keyboard, if keyboard is out of inverter, it will not finish copy operation, and needs to
retry it.
3. When sending data to inverter, if keyboard is out of inverter,, it will not finish download operation and needs
to retry it.
4. When sending data to keyboard, current state of inverter will not be remained. And all keys are invalid when
sending data to inverter.
5. If it displays E.CEP, operation of copy parameter will be interrupted and needing to retry it. Press STOP
button to return monitor menu.
6. When software is not compatible,it shows E.EDI,and will not send data to inverter.
F4.06
Keyboard potentiometer lower
F4.07
limit
Keyboard potentiometer lower
F4.08
limit corresponding setting
Keyboard potentiometer upper
F4.09
limit
Keyboard potentiometer upper
F4.10
limit corresponding setting
Keyboard potentiometer lower limit: It defines the lower limit of the signal given by potentiometer. Inverter treats the
voltage lower than this value as the lower limit signal.
Keyboard potentiometer lower limit corresponding setting: It sets ratio of keyboard potentiometer lower limit.
Keyboard potentiometer upper limit: It defines the upper limit of the signal given by potentiometer. Inverter treats the
voltage higher than this value as the lower limit signal.
Keyboard potentiometer upper limit corresponding setting: It set ratio of keyboard potentiometer upper limit.
Setting range: 0-2
Copy the parameter group F0 to Fd to the keyboard and
download the copied data of the keyboard into the inverter.
Reserved
Setting range: 0.00-5.00V
Setting range: 0.00-100.00%
Setting range: 0.00-5.00V
Setting range: 0.00-100.00%
115
FUNCTION PARAMETER SPECIFICATION
Factory default: 0
Factory default: 0.50V
Factory default: 0.00%
Factory default: 4.50V
Factory default: 100.00%