AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
asynchronous motor VF debugging procedure
Set start command, using local keyboard to set frequency and command
channel related function code F0.02,F0.03,F0.09,F0.14,F0.15;
Set motor parameter and select VF curve, related function code F5.01-F5.06,F8.00
No load debugging from low speed to high speed and check if current
stable and normal or not, check if the motor speed is stable or not
Normal or not?
Yes
on load debugging from low speed to high
speed and check if current stable and normal
or not, check if the motor speed is stable or not
Normal or not?
Yes
Debugging ends and set other parameters
according to the users' requirements
Chart 4-22 asynchronous motor VF debugging procedure
F0.00=4
No
No
BASIC OPERATION AND TRIAL RUN
1 if low frequency torque is not enough, rise F8.12 and debug
2 if there're current fluctuation and instable motor speed, adjust F8.28,
F8.29 to debug; press SET, self tuning waiting state
3 if there's OV during speed DEC, adjust FA.00-FA.02 to debug;
check FA.08-FA.09 settings if there's energy braking resistance.
4 adjust F8.30-F8.32 if there's overload or OC fault.