8.6 Motor Parameters

F5.00
Motor type
Motor type: Read-only parameter that indicates the current motor type, which is based on [F0.00] or [F5.31] motor
control mode.
0: asynchronous motors (AM);
1: Synchronous Motor (PM)
F5.01
Motor rate
F5.02
Motor rated power
F5.03
Motor rated frequency
F5.04
Motor rated speed
F5.05
Motor rated voltage
F5.06
Motor rated current
Set nameplate parameters; every time when motor rated power setting is changed, the inverter will automatically adjust
default parameter as the [F5.03-F5.11] default. If self-study, parameters of [F5.07-F5.11] will automatically change
according to the result of self-study. If high accuracy motor control is needed, please implement motor self study after
correct setting of parameter [F5.01-F5.06].
F5.07
Motor no-load current
F5.08
Motor stator resistor
F5.09
Motor rotor resistor
F5.10
Motor stator inductance
Stator mutual
F5.11
inductance
Asynchronous motor model parameter, when set [F5.12] parameters after the Auto-tuning, [F5.07 ~ F5.11] content will
automatically change. If you know the exact parameters of the motor model, parameters self-tuning is not necessary;
manually inputting the motor model parameters for commissioning.
Parameters self-tuning
F5.12
selections
0: No operation: Set as default without self study.
1: Rotary type self-study: Before self tuning, please correctly input the parameter value [F5.01-F5.06] of
asynchronous motor which is controlled. During rotary tuning, firstly, asynchronous motor at static state, it automatically
detects motor stator resistance, motor rotor resistance, motor stator &rotor inductance. Then the asynchronous motor at
rotate state, it automatically detects motor no-load current, motor stator &rotor mutual inductance. All results will be auto
written in [F5.08], [F5.09], [F5.10] and [F5.07],[F5.11] and renewed when rotary tuning is over. After parameter setting,
press FWD key to start self study, keyboard LED display "t-01". Motor automatically stops when self tuning is over.
Inverter recovers to standby state.
2: static type self-study: Before self tuning, please correctly input the parameter value [F5.01-F5.06] of asynchronous
motor which is controlled. During static tuning, motor at static state, it automatically detects motor stator resistance,
motor rotor resistance, motor stator &rotor inductance. All results will be auto written in [F5.08], [F5.09], [F5.10] and
renewed when static tuning is over. After parameter setting, press FWD key to start self study, keyboard LED displays
"t-02".FWD indicator is off when self tuning is over. Inverter recovers to standby state.
Note: [F5.12] is automatic set as 0 after self tuning.
Attention: 1. Before setting [F5.12] as 1 –self study, unload the motor firstly.
2. In some occasions (such as can't unload), if it can't self study or it is not high control accuracy required,
Setting range: 0-1
Setting range: 2-48
Setting range: 0.4-1000.0kW
Setting range: 0.01Hz-max frequency
Setting range: 0-65000rpm
Setting range: 0-1500V
Setting range: 0.1-2000.0A
Setting range:0.01-650.00A
Setting range:0.001-65.000
Setting range:0.001-65.000
Setting range:0.1-6500.0mH
Setting range:0.1-6500.0mH
Setting range: 0-2
117
FUNCTION PARAMETER SPECIFICATION
Factory default:0
Factory default: 4
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: mode setting
Factory default: 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents