8.11 PID Parameters

PID control is a common method used in process control. Through a series of proportional, integral and derivative
calculations on the value difference between the controlled object feedback and inverter PID feedback to adjust the
output frequency of the inverter, which forms the negative feedback PID regulation to stabilize the controlled object
within the PID given value.
Fb.00
PID controller given signal source
Set the input channel of PID controller given signal.
0: Keyboard number PID given: Decided by [Fb.01] setting.
1: Keyboard potentiometer: given by keyboard potentiometer
2: Terminal VS voltage analog: given by terminal VS voltage analog
3: Terminal AI analog: given by terminal AI analog
4: Terminal AS current analog: given by terminal AS current analog
5: Terminal PUL pulse signal: given by terminal PUL pulse signal
6: RS485 communication: given by RS485 communication; communication address is 0x3008/0x2008
7: Optional card: given by optional card; see optional card manual
8: Terminal selection: given by multifunctional input terminal combination set by [F2.00-F2.07].
Terminal switch table:
Terminal 3
Terminal 2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Any doubt please see "FC" parameter group which is about multispeed time sequence.
LED "0000" digit: reserved
See input terminal chart
See output terminal chart
Please see malfunction code table
Please see malfunction code table
Setting range: 0-9
Terminal 1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
FUNCTION PARAMETER SPECIFICATION
PID giving terminal switch selection
Keyboard number give PID
Keyboard potentiometer
Terminal VS voltage analog
Terminal AI analog
Terminal AS current analog
Terminal PUL pulse signal
RS485 communication
Optional card
133
--
--
--
--
Factory default: 0