F1.29
Power off restart action selection
F1.30
Power off restart waiting time
Power off restart action selection:
0: Invalid: Only run with order for power on again. When keyboard operation control, RS485 communication control or
optional card control is working, the running order would be automatically cleared when power off.
When external terminal control, run as [F1.31] setting.
1: Valid If inverter is at run state before power off, it start automatically after [F1.30] waiting time. When waiting, it does
not accept any orders. But if inputting stop order, it will not restart.
Note: Power off restart action selection can make machine automatic re-start when power recovers. Please use
it carefully.
Power off restart waiting time: When [F1.29] setting is valid, inverter restarts after [F1.30] waiting time. The setting
principle of the time is mainly based on the related recovery preparation time after power restoration.
Terminal running protection
F1.31
selection
After selecting terminal operation, the initial state of the peripheral device wiring may affect the device safety, which
would provide protective measures for terminal operation.
LED "0" digit: when electrifying, terminal operation command selection
Implement operation command when electrifying and when the terminal operation command is valid.
0: Terminal running order invalid: when electrifying terminal controls stop firstly and then restart.
1: Terminal running order valid: when electrifying terminal controls start directly
LED "00" digit: when switch the running order give channel
Select running order channel switching to terminal order when the terminal operation command is valid; Implement
operation command method
0: invalid Terminal controls stop firstly and then restart.
1: valid Terminal controls start directly.
F1.32
JOG running frequency setting
F1.33
JOG ACC time
F1.34
JOG DEC time
JOG running frequency setting: Set output frequency when JOG.
JOG ACC time: When [F1.13] LED"0"digit is 0, it means the time need for output frequency ACC from 0.00Hz to max
frequency [F0.09]. When [F1.13] LED"0"digit is 1, it means the time need for output frequency ACC from 0.00Hz to
50.00Hz. Details see [F1.13].
JOG DEC time: When [F1.13] LED "0"digit is 0, it means the time need for output frequency DEC from max frequency
[F0.09] to 0.00Hz. When [F1.13] LED "0"digit is 1, it means the time need for output frequency DEC from 50.00Hz to
0.00Hz.
Note: JOG run frequency set is only limited by [F0.09]. When JOG frequency setting is bigger than [F0.11]
upper limitation, actual JOG output frequency is limited by upper limitation. Only terminal JOG priority is
not limited by run order channels. Other JOG orders have priority only when the channel is the same as
others. Such as keyboard JOG is only valid under keyboard control.
Setting range: 0-1
Setting range: 0.00-120.00s
Setting range :0000-0011
Setting range: 0.00-Max frequency
Setting range: 0.01-650.00s
Setting range: 0.01-650.00s
92
FUNCTION PARAMETER SPECIFICATION
Factory default: 0
Factory default: 0.50s
Factory default: 11
Factory default: 5.00Hz
Factory default: 10.00s
Factory default: 10.00s