AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
LED"00"digit: Time unit
0: second
1: minute
2: hour
LED"000"digit: Power down storage mode
0: no storage
1: storage
This parameter is defined as when the selection process is running, the inverter power whether to store the current
state of the running program (running stages, the remaining time of this stage, deceleration and direction of travel, etc.).
If you choose power down storage, the "000"digit of [FC.15] defines the way power is restored of the next running. To
ensure sustainable state of inverter after power recovery, the parameter should be set as "1".
LED"0000"digit: Start-up mode
0: Restart from the 1st step
1: Restart from the step when stop
2: Continue from the time when stop
Set restart mode when stop for some reasons (stop, fault, power off and so on).
Choosing 0: Restart from the 1st step
Choosing 1: Restart from the step when stop
Choosing 2: Continue from the time when stop
Note: Output frequency is limited by upper/lower limit frequency. When frequency is lower than lower limit
frequency, it runs as [F0.13] lower limit frequency mode.
FC.16
PLC 1st step running time
FC.17
PLC 2nd step running time
FC.18
PLC 3rd step running time
FC.19
PLC 4th step running time
FC.20
PLC 5th step running time
FC.21
PLC 6th step running time
FC.22
PLC 7th step running time
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
Setting range: 0.0-6500.0(s/m/h)
140
FUNCTION PARAMETER SPECIFICATION
Factory default: 10.0
Factory default: 10.0
Factory default: 10.0
Factory default: 10.0
Factory default: 10.0
Factory default: 10.0
Factory default: 10.0