Veichi AC100-T3-1R5G Manual page 28

High-performance vc frequency inverter
Table of Contents

Advertisement

AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
Auxiliary Terminal Output Capacity
Terminal
10V auxiliary power supply output, constitutes loop
+10V
with GND.
A01/A02
Analog monitor output, constitutes loop with GND.
24V auxiliary power supply output, constitutes loop
+24V
with COM.
Collector open circuit output; can set the
Y
action-object by program.
TA1/TB1/TC1
Passive connector output; can set the action-object
TA2/TB2/TC2
by program.
Chart 3-4:AC100 Series Inverter Auxiliary Terminals Output Capacity
●Connection Function Specification of Switch Terminals
Switch
Selecting
Treminal
Position
K1
S1
K2
K3
S2
K4
K5
S3
K6
K7
S4
K8
J1
S5
J2
J3
Function Definition
AS
+10V
VS
AI
GND
A+
B-
AO2
AO1
GND
COM
X1
X2
Function Specification
AO1:0~20mA or 4~20mA current output
AO1:0~10V voltage output
AI:0~20mA or 4~20mA input current
AI: 0~10V input voltage
AO2: 0.0~50kHz (J1 on), open collector circuit output
AO2:0.0~50kHz (J1 on), active source output
RS485: connect with 120Ω terminal resistor
RS485:connect without 120Ω terminal resistor
AO2:0.0~50kHz frequency output
AO2:0~20mA or 4~20mA current output
AO2:0~10V voltage output
PLC
TA1
TB1
Y
+24V
COM
X3
X4
X5
X6
X7/PUL
TA2
TB2
25
INSTALLATION AND WIRING
Max Output
50mA
Max output 2mA as frequency,
voltage signal,
100mA
DC24V/50mA
3A/240VAC
5A/30VDC
TC1
TC2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents