AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
F1.35
Jump frequency
F1.36
Jump frequency range
Jump frequency: When running, the frequency avoid running.
Jump frequency range: The up/down frequency range of [F1.35] avoid running.
When the inverter is running with load, in order to avoid resonance frequencies of mechanical load for the output
frequency, jump frequency can be used to avoid the resonance. The inverter can set one jump point to implement the
jumping and after setting the skip frequency parameters, even if the drive frequency is within the given point of the
mechanical resonance frequency of the load, the output frequency of the inverter will be automatically adjusted to the
resonance frequencies of the external mechanical load in order to avoid running on the resonance point.
Note: Output frequency will jump through frequency area when ACC/DEC.

8.3 Quantum Digital Terminal Parameter

F2.00
Multifunction input terminal 1(X1)
F2.01
Multifunction input terminal 2(X2)
F2.02
Multifunction input terminal 3(X3)
F2.03
Multifunction input terminal 4(X4)
F2.04
Multifunction input terminal 5(X5)
F2.05
Multifunction input terminal 6(X6)
F2.06
Multifunction input terminal 7(X7)
There're seven multifunction terminals(X1-X7) which can be defined by [F2.00-F2.06]. the feature and filter time can be
defined by [F2.08-F2.11].
X7 is sharing an external input terminal X7 / PUL with the high-speed pulse input; when there is a timing function code
selection PUL given, the PUL input as external terminals, otherwise input as X7 input. For example, when [F0.03] = 5,
the terminal X7 / PUL would be valid as PUL input, and the switch signal input X7 would not be accepted.
Note: the seven multi-function input terminals actually exist, in order to avoid the repetition of the input
terminal selection function, the actual setting will be against each other; for example, when [F2.00] = 1, the
F2.01 can't be set as 1 and it can only be set as any other value that is not within [F2.00] , [F2.02 ~ F2.06] and
[F2.69 ~ F2.71].
Multi-function input terminals can be easily set and chosen according to needs. Settings and functions in the table
below:
Setting range: 0.00-Max frequency
Setting range: 0.00-Max frequency
Setting range: 0-47
93
FUNCTION PARAMETER SPECIFICATION
Factory default: 0.00Hz
Factory default: 0.00Hz
Factory default:1
Factory default:2
Factory default:4
Factory default:5
Factory default:6
Factory default:8
Factory default:10