AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
Must meet:0≤F1≤F2≤F3≤F4≤F5≤max frequency,0≤V1≤V2≤V3≤V4≤V5≤100.0%
V1,V2,V3,V4,V5 is based on motor rated voltage.
F8.11
Output voltage percentage
Output voltage adjustment coefficient adjusts output voltage of inverter to meet different V/F requirement.
F8.12
Torque boost
F8.13
Torque boost cut-off frequency
Torque boost: Improve low frequency torque trait by voltage compensation. Please set it rightly. If too high, motor
maybe happens over excitation at low frequency running, over heat when long time, even over current protection or
can't start normally.
Note: when [F8.00] is 1, [F8.12] is invalid.
Torque boost cut-off frequency: Set torque boost valid range. When output frequency exceeds this value, torque
boost function stop. 100% is corresponding to motor rated frequency.
Setting range: 25-100%
Setting range: 0.1-30.0%
Setting range: 0.0-100.0%
126
FUNCTION PARAMETER SPECIFICATION
Factory default :100%
Factory default :Accord model
Factory default :20.0%