8.9 V/F Control Parameters

V/F curve selection
F8.00
V/F curve selection: used to select the V/F curve types to meet different load requirements.
0: linear V/F curve
1-9: 1.1-1.9 respectively VF power curve, as shown below;
10: VF square curve;
11: Custom VF curve; see [F8.01-F8.10];
VF default linear curve for most common situations; multi-idempotent curve and square VF curve are generally used for
VF fans or pumps to reduce the high-frequency current to achieve energy savings.
Note: multi-idempotent curve and square VF curve are calculated from the initial frequency set in F8.11, see
F8.15
F8.01
Self-setting voltage V1
F8.02
Self-setting frequency F1
F8.03
Self-setting voltage V2
F8.04
Self-setting frequency F2
F8.05
Self-setting voltage V3
F8.06
Self-setting frequency F3
F8.07
Self-setting voltage V4
F8.08
Self-setting frequency F4
F8.09
Self-setting voltage V5
F8.10
Self-setting frequency F5
Self-setting V/F curve: Users set the 1
frequency based on rated output voltage 100%. Users set the 1
V1/V2/V3/V4/V5.
Setting range:0-4
Setting range: 0.0-100.0%
Setting range: 0.00-max frequency
Setting range: 0.0-100.0%
Setting range: 0.00-max frequency
Setting range: 0.0-100.0%
Setting range: 0.00-max frequency
Setting range: 0.0-100.0%
Setting range: 0.00-max frequency
Setting range: 0.0-100.0%
Setting range: 0.00-max frequency
/2
/3
/4
/5
voltage ratio of V/F curve corresponding to F1/F2/F3/F4/F5
st
nd
rd
th
th
/2
st
125
FUNCTION PARAMETER SPECIFICATION
/3
/4
/5
frequency of V/F curve corresponding to
nd
rd
th
th
Factory default 0
Factory default 3.0%
Factory default 1.00Hz
Factory default 28.0%
Factory default 10.00Hz
Factory default 55.0%
Factory default 25.00Hz
Factory default 78.0%
Factory default 37.50Hz
Factory default 100.0%
Factory default 50.00Hz