Veichi AC100-T3-1R5G Manual page 54

High-performance vc frequency inverter
Table of Contents

Advertisement

AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
parameters self tuning
self tuning fails no motor
parameter updated
Detect fault reasons and
retest after recovery
Confirm power connected correctly and motor wiring and electrifying correctly
Set according to the motor nameplate and wiring mode F5.01
Set motor rated power according to the nameplate F5.02
Set motor rated frequency according to the nameplate F5.03
Set motor rated speed according to the nameplate F5.04
Set motor rated voltage according to the nameplate F5.05
Set motor rated current according to the nameplate F5.06
Yes
If motor can disengage load test
rotary self study, set F5.12 = 1
press SET , waiting state
Press FWD, self tuning start
Yes
If fault alarm?
self tuning over, auto updating of motor
parameter F5.07-F5.11 and save
Chart 4-21: motor parameter self tuning
BASIC OPERATION AND TRIAL RUN
Start
No
static self study, set F5.12 = 2
press SET a, waiting state
No
End