AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
F0.09
Max frequency output
Upper limitation source
F0.10
selection
F0.11
Number give upper limitation
F0.12
Lower limitation
F0.13
Lower limitation run mode
Max frequency output: The max frequency the frequency inverter permit to set. When [F1.13] LED "0" digit is 0, it is
also the base of ACC/DEC time setting.
Upper limitation source selection: To select the give source of upper frequency limitation of frequency inverter. It is
the max output frequency limitation set according to the machinery max rotate speed.
0: Upper limit number given Upper limitation set by [F0.11]. Max setting is small or equal to max frequency [F0.09].
Min setting is bigger or equal to min frequency [F0.12].
1: Keyboard potentiometer Upper limitation set by keyboard potentiometer.
2: Terminal VS voltage analog Upper limitation set by VS input analog.
3: Terminal AI voltage analog Upper limitation set by AI input analog.
4: Terminal AS current analog Upper limitation set by AS input analog.
5: Terminal pulse PUL given Upper limitation set by PUL input pulse frequency.
6: RS485 communication given Upper limitation set by RS485 communication (0x3004/0x2004) .Max set is not over
max frequency [F0.09]. Min set not lower than [F0.12]. Details refer to Fd communication control parameter group and
appendix 2: Modbus communication protocol, communication given upper frequency (0x3004 / 0x2004).
Note: Relation between input analog or PUL pulse frequency and upper limit frequency: when input max valid
value, upper limit frequency is max frequency [F0.09]. When input min valid value, upper limit frequency is
0.00Hz.
Number setting of upper limitation: It is the upper limit frequency given channel when [F0.10] is set as 0.
Lower limitation: It is the lower limitation of output frequency. When given frequency is lower than this value, [F0.13]
decides the run frequency.
Lower limitation run mode
0: Stop: When actual given frequency is lower than the lower limitation, inverter runs at 0.00Hz.
1: Run as lower limitation: When actual given frequency is lower than the lower limitation, inverter run at the lower
limitation.
Note: 1. Given upper limitation by analog or PUL pulse frequency, lower limitation is invalid if upper limitation
is lower than lower limitation.
2. Max frequency, upper limitation and lower limitation set carefully according to actual need please.
Except upper limitation and lower limitation, inverter is also limited by parameters set such as start
frequency, free stop frequency, stop DC brake start frequency and so on. Max frequency, upper
limitation and lower limitation relationship as below:
Setting range: 0.00-320.00Hz
Setting range: 0-6
Setting range: Lower limitation-max
output frequency
Setting range: 0.00-upper limitation
Setting range: 0-1
82
FUNCTION PARAMETER SPECIFICATION
Factory default: 50.00Hz
Factory default:0
Factory default: 50.00Hz
Factory default: 0.00Hz
Factory default: 1