Veichi AC100-T3-1R5G Manual page 106

High-performance vc frequency inverter
Table of Contents

Advertisement

AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
F2.32
Output frequency level 1(FDT1)
F2.33
FDT1 lag
F2.34
Output frequency level 2(FDT2)
F2.35
FDT2 lag
The parameter is used to set frequency test level. When output frequency reaches or exceeds the set value of
[F2.32]/[F2.34], FDT 1/2 terminal outputs signal after [F2.33]/[F2.35] delay frequency. When output reaches or lower
than the set value of [F2.32]/[F2.34], FDT 1/2 terminal stops output signal after [F2.33]/[F2.35] delay frequency.
Given frequency reaches
F2.36
checkout range
When output frequency reaches or approaches the given frequency, output terminal Y/TA1-TB1-TC1/TA2-TB2-TC2
output valid signal if it is selected as "given frequency reached". This function can used to adjust the test range offset.
give frequency
output frequency
frequency arrive
output signal
F2.37
Over load pre alarm level
F2.38
Over load pre alarm delay
When output current exceeds [F2.37] setting continuously, the output terminal outputs valid signal after [F2.38] delay
frequency. When output current is lower than [F2.37] setting, the output terminal outputs invalid signal after [F2.38]
delay frequency.
F2.39
Under load pre alarm level
F2.40
Under load pre alarm delay
When output current is equal to or lower than [F2.39] setting, the output terminal outputs valid signal after [F2.40] delay
frequency. When output current is higher than [F2.39] setting, the output terminal outputs invalid signal after [F2.40]
delay frequency. 100.00% corresponding to motor rated current.
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
Setting range: 0.00- Max frequency
Setting range: 0.00-50.00Hz
ON
frequency arrive test show
Setting range: 0.0-200.0%
Setting range: 0.0-100.0s
Setting range: 0.0-200.0%
Setting range: 0.0-100.0s
103
FUNCTION PARAMETER SPECIFICATION
output frequency
ON
Factory default: 30.00Hz
Factory default: 0.00Hz
Factory default: 50.00Hz
Factory default: 0.00Hz
Factory default: 0.00Hz
frequency arrive
checkout range(F2.36)
time
Factory default: 180.0%
Factory default: 0.5s
Factory default: 30.0%
Factory default: 0.5s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents