Veichi AC100-T3-1R5G Manual page 137

High-performance vc frequency inverter
Table of Contents

Advertisement

AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
Fb.01
Keyboard number give PID
This function is valid only when [Fb.00]/[Fb.02] is set as keyboard number given/feedback. It is based on feedback
signal max range [Fb.04]. After this parameter is changed, PID given in monitor object is modified automatically at the
same time.
If [Fb.04] LED "0" is set as 3, this value can be modified by UP/DW key. Whether save the modification is decided by
[F4.04] LED "00" digit.
Fb.02
PID feedback signal source
Set PID controller feedback signal input channel:
0: Keyboard number PID feedback: PID feedback channel decided by [Fb.01].
1: Keyboard potentiometer feedback: Keyboard potentiometer feedback channel
2: Terminal VS voltage analog feedback: Terminal VS voltage analog feedback channel
3: Terminal AI voltage analog feedback: Terminal AI voltage analog feedback channel
4: Terminal AS current analog feedback: Terminal AS current analog feedback channel
5: Terminal PUL pulse signal feedback: Terminal PUL pulse signal feedback channel
6:RS485 communication feedback: PID feedback channel decided by RS485.Communication address is
0x3009/0x2009.
7: Optional card: optional card PID feedback channel; see optional card manual
8: Terminal selection: PID feedback channel decided by multifunction input terminal combination. Multifunction input
terminal is set by [F2.00-F2.07].
Terminal switch table:
Terminal 3
Terminal 2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Any doubt please see "FC" parameter group which is about multispeed time sequence.
Note: PID controller given signal source and PID controller feedback signal source can't be the same.
Otherwise PID can't work normally.
Fb.03
Feedback signal gain
It is used to magnify or reduce feedback channel input signal.
Feedback signal max
Fb.04
measuring range
It is used to revise the display data of PID given and PID feedback.
Setting range: 0.00-100.0%
Setting range:0-8
Terminal 1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
Setting range: 0.00-10.00
Setting range: 0-100.0
FUNCTION PARAMETER SPECIFICATION
PID giving terminal switch selection
Keyboard number give PID
Keyboard potentiometer
Terminal VS voltage analog
Terminal AI analog
Terminal AS current analog
Terminal PUL pulse signal
RS485 communication
Optional card
134
Factory default: 50.0%
Factory default:2
Factory default:1.00
Factory default:100.0