AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
F2.29
Output terminal 1(Y)
F2.30
Relay output terminal (TA1-TB1-TC1)
F2.31
Relay output terminal (TA2-TB2-TC2)
0: No output
1: Running
2: REV running
3: Fault trip alarm 1(alarm when fault self-recover)
4: Fault trip alarm 2(no alarm when fault self-recover)
5: In the fault retry
6: External fault stop
7: Under voltage: The frequency converter displays "E.LU1/2" for the voltage is excessively low, output signal.
8: inverter operation preparation completed
9: Output frequency level test 1(FDT1)
10: Output frequency level test 2(FDT2) When the output frequency of frequency converter is over test level
[F2.32]/[F2.34] setting, it outputs valid signal after [F2.33]/[F2.35] delay frequency. When output frequency is lower
than test level, it outputs invalid signal after delay frequency. Details see [F2.32-F2.35].
11: Reaching given frequency Details see [F2.36].
12: Run with 0 speed
13: Upper frequency limit reached
14: Lower frequency limit reached
15: Program running cycle completed: One cycle finished, it output 500ms signal.
16: Program running step completed
17:PID feedback over upper limit When PID feedback arrive [Fb.16] and still over limit after [Fb.14] delay time, it
output valid signal.
18:PID feedback under lower limit When PID feedback arrive [Fb.17] and still over limit after [Fb.14] delay time, it
output valid signal.
19: PID feedback sensor wire break Details see [Fb.14-Fb.17].
20: Pre alarm for motor overload
21: Timer time reach Details see [F2.25-F2.26].
22: Counter reach biggest value Details see [F2.27-F2.28].
23: Counter reach set value Details see [F2.27-F2.28].
24: Energy braking Details see [FA.08].
25: PG feedback break Details see [F5.15-F5.17].
26: Emergency stop
27: Pre alarm output for over load It output valid signal when output current arrive or over [F2.37] and after [F2.38]
delay time.
28: Pre alarm output for under load It output valid signal when output current is smaller or equal to [F2.39] and after
[F2.40] delay time.
Note:
1, Relay output terminal TA1-TC1 on and TB1-TC1 off is valid signal. Relay output terminal TA2-TC2 on and
TB2-TC2 off is valid signal. Y output terminal with low electrical level combined with (+24V) terminal outputting
24V power is valid signal.
2, To ensure the output terminal selection function key physical presence of non-duplicative, the actual
settings would against each other, such as when [F2.29] = 1 the F2.30 will not be set to 1 instead it or [F2.31] or
[F2.74-F2.75].
FUNCTION PARAMETER SPECIFICATION
Setting range: 0-28
102
Factory default: 0
Factory default: 1
Factory default: 3