AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
E.oU2
E.oU3
E.oU4
E.oC1
E.oC2
E.oC3
E.oL1
Deceleration time is too
●
short.
Dec
Load potential energy or
●
overvoltage
inertia is too large.
Power voltage fluctuation
●
over limit.
Constant
Power voltage fluctuation
●
speed over-
over limit.
voltage
Over-voltage
Power voltage fluctuation
●
when stop
over limit.
Acceleration time is too
●
short.
Start motor when running.
●
Acc
V/F curve setting is not
●
over-current
suitable. Or torque boost
too high.
Inverter capacitance is too
●
small.
Deceleration time is too
●
short.
Dec
Load potential energy or
●
over-current
inertia is too large.
Power voltage fluctuation
●
over limit.
Constant
Sudden load change.
●
speed
Power grid voltage is too
●
over-current
low.
V/F curve setting is not
●
suitable. Or torque boost
too high.
Power grid voltage is too
●
low.
Motor
Wrong overload protection
●
over-load
setting.
Locked-rotor run or too
●
heavy load.
Universal motor runs at
●
low speed for a long time
FAULT DIAGNOSES AND PROCESSING
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
57
Prolong deceleration time
properly.
Reduce load inertia or improve
inverter capacitance or add
braking unit.
Detect input power and clear
fault.
Detect input power voltage and
eliminate fault.
Install input reactor.
Check input power, eliminate
fault.
Seek support from vendor.
Prolong acc time.
Restart motor until it totally
Stop; Set F1.00 to 1or 2.
Reset V/F curve or torque
boost value.
Select inverter with right
capacitance.
Prolong deceleration time.
Connect external braking
resistance or braking unit.
Select inverter with right
capacitance.
Check load change and
eliminate it.
Check input power, eliminate
fault.
Reset V/F curve or torque
boost value.
Check input power, eliminate
fault.
Unreasonable F5.06 setting.
Adjust load or select inverter
with right capacitance.
If long-term low-speed
operation is needed, please
choose special motor for
inverter.