AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
Check if it meets the requirement of
Surroundings
table3-1.
Check if the inverter or the motor heat or
Cooling system
change color abnormally and cooling fan
working state.
Motor
Check if there is abnormal vibration or noise.
Check if output current is over the rated
Load
value of the motor or the inverter and has
lasted for a period.
No operation under power connecting state. Otherwise, there is danger of electric shock even death.
Before operating, please cut all related equipments power, ensuring that the main circuit DC current has
dropped to safe range. And please operate after 5 mins.
Regular Inspection
●
On normal cases, do one inspection every 3 or 4 months. Please decide the actual inspection period according to the
machine use condition and working circumstance when using the machine.
Main Circuit
●
Items
Overall
Electric connection
Mechanical connection
Semi-conductive
component
Electrolytic capacitor
Peripheral equipment
PCB
Cooling system
Checking Content
Check insulated resistance;
Check environment.
Check if the color of wire and
●
connector changes and if there is
disrepair, crack color change or
aging in insulating layer.
Check if the connect terminals are
●
frayed, damaged or loose.
Earth checking.
●
Check if there is abnormal vibration
●
or noise or anything loose.
Check if there is dust or rubbish.
●
If there is obvious change of
●
appearance?
If there is liquid leak, color change or
●
crack. If the safety valve outcrop,
inflation, creak or liquid leak.
Peripheral equipment outlook and
●
insulation checking.
check if there're peculiar smell, color
●
change or bad rust and check if the
connection is right.
Check if the fan is damaged or
●
blocking.
If rubbish and dust is stick to the
●
heat sink.
PERIODIC OVERHAUL AND MAINTENANCE
Find out the problem and solve it.
Check if it overloads. Tighten screw. Check
if cooling fan is dirty or stall rotate.
Tighten machine and electric connection
and lubricate the machine components.
Check if it overloads and if the machine
model is right.
Tighten and change bad component;
Clear and improve circumstance.
Change bad wire.
●
Fasten terminals and change bad
●
terminals.
Measure earth resistance and fasten
●
earth terminals.
Tighten, lubricate and change the bad
●
components.
Clean operation environment
●
Change damaged component
●
Change damaged component
●
Clear and change damaged component.
●
Fasten connector
●
Clear PCB
●
Change damaged PCB
●
Clean operation environment
●
Change damaged component.
●
68
Treatment Measure