AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
E.oL2
E. SC
E.oH1
E.oH2
E.Fb1
E.Fb2
E.TE1
Load is too heavy.
Acceleration time is too
short.
Inverter
Start motor when running.
over-load
V/F curve setting is not
suitable. Or torque boost
too high.
Acceleration time is too
short.
Short circuit between
inverter output phases or
System
earth.
abnormal
Module is damaged.
Electromagnetic disturb.
Temperature is too high.
Air channel is blocked.
Fan connection parts
Inverter
loose.
over-heat
Fan is damaged.
Temperature detection
circuit fault
Temperature is too high.
Air channel is blocked.
Fan connection parts
Rectifier
loose.
over-heat
Fan is damaged.
Temperature detection
circuit fault
PID feedback wire breaks.
PID feedback
PID feedback channels
over upper
parameter is wrong.
limit
Analog feedback channel
is abnormal.
PID feedback wire breaks.
PID feedback channels
PID feedback
parameter is wrong.
over lower
Analog feedback channel
limit
is abnormal.
Detection overtime
Start static detection when
Motor static
motor is running.
detection fault
Capacitance difference is
too big between motor
and inverter.
FAULT DIAGNOSES AND PROCESSING
58
Select inverter with right
capacitance.
Prolong acceleration time
Restart motor until it totally
stops. Set [F1.00] as 1or2.
Reset V/F curve or torque
boost value.
Prolong acceleration time
properly.
Check peripheral equipments
and restart after fault
eliminating.
Seek support from vendor.
Check system wiring, earth,
shield and deal as required.
Meet the environment
requirement.
Clear the air channel.
Check and reconnect the wire
Change the same new fan.
Seek support from vendor.
Meet the environment
requirement.
Clear the air channel.
Check and reconnect the wire.
Change the same new fan.
Seek support from vendor.
Check PID feedback wire.
Check the PID feedback
channel parameter setting.
Seek support from vendor.
Check PID feedback signal
wire.
Check the PID feedback
channel parameter setting.
Seek support from vendor.
Check motor connection wire.
Detect after motor stops totally.
Change inverter model.
Reset parameter according to
nameplate.