AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
would start.
During deceleration, when a given frequency is less than shutdown DC braking start frequency, start DC braking and
the output frequency will jump to zero. If there's no strict requirement for operating conditions, the DC brake start
frequency should be set as low as possible
Stop DC braking current: It is the current that inverter give motor when DC braking. It is based on the output rated
current of the inverter. DC braking can afford 0 speed torque. It is usually used for improve stop accuracy and quick
stop. It can't be used for DEC braking for normal running.
Waiting time of stop DC braking: It is the time for waiting to DC braking when inverter DEC to initial frequency of stop
DC braking and stop output.
Stop DC braking duration: It is DC braking current holding time after stop. It is no DC braking process when braking
time is 0.0s.
F1.12
F1.13
ACC/DEC mode selections
F1.14
Start ACC rate of S curve
F1.15
Start DEC rate of S curve
ACC/DEC mode selections
LED "0" digit: ACC/DEC time base
0: max frequency Base is max frequency [F0.09]
1: fixed frequency Base is 50.00Hz
LED "00" digit: ACC/DEC mode
0: straight line Suitable for general load.
1: S Curve Suitable for load need reduce noise, vibration, impact or load need descend torque for low frequency and
ACC short time for high frequency. If over current or over load when start, please increase [F1.14] setting.
LED "000" digit: reserved
LED "0000" digit: reserved
Start ACC rate of S curve: It is the rate when start ACC. The smaller the rate is, the ACC S curve is sharper.
Otherwise, the bigger the rate is, the ACC S curve is more like a beeline. If you want it ACC more smoothly, you can
reduce the rate and prolong ACC time.
Start DEC rate of S curve: It is the rate when start DEC. The smaller the rate is, the DEC S curve is sharper.
Otherwise, the bigger the rate is, the ACC S curve is more like a beeline. If you want it DEC more smoothly, you can
reduce the rate and prolong DEC time.
Reserved
Setting range: 0000-0011
Setting range: 20.0%-100.0%
Setting range: 20.0%-100.0%
89
FUNCTION PARAMETER SPECIFICATION
Factory default: 0000
Factory default: 50.0%
Factory default: 50.0%