AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
Setting
0
No function( can choose again)
1
FWD
2
REV
3
3 line running control(Xi)
4
FWD JOG
5
REV JOG
6
Free stop
7
Emergency stop
8
Fault reset
9
Out fault input
10
Frequency (UP)
11
Frequency (DW)
12
(UP/DW clear )
13
Reserved
14
Reserved
15
Multi speed terminal 1
16
Multi speed terminal 2
17
Multi speed terminal 3
18
Multi speed terminal 4
19
ACC/DEC time selection terminal 1
20
ACC/DEC time selection terminal 2
21
ACC/DEC pause
22
PID control cancel
23
PID control pause
0: No function: it means terminal invalid. If the terminal function is idle, it is recommended to set "0" to prevent the
occurrence of misuse.
1: FWD When run order is given by terminal, and [F2.12] is set as 2 line 1, and when the terminal is valid, inverter will
FWD. Other control mode, please refer to [F2.12].
2: REV When run order is given by terminal, and [F2.12] is set as 2 line 1, and when the terminal is valid, inverter will
REV. Other control mode, please refer to [F2.12].
3: 3 line run control (Xi): When the run order is given by terminal, and [F2.12] is set as 3 line 1/2, it is 3 line run control
(Xi). Details refer to [F2.12].
4: FWD JOG
5: REV JOG
When the terminal is valid, the inverter jogs forward. Terminal jog command has the highest priority. Jog parameters
detailed settings see [F1.32-F1.34].
6: Free stop: When it is valid, inverter stops output. Motor will free run. When free stop terminal is always valid, inverter
does not accept any start order and keep stop state. Whether recover to original order after free stop order is relieved
when terminal 2 line control running, refer to [F2.13] please. It does not recover to original order after free stop order is
relieved when keyboard, RS485, optional card and terminal 3 line control running. If need start inverter, it needs to input
run order again.
7: Emergency stop If input emergency stop order when running, inverter DEC and stop according [F1.24] DEC time
Setting
FUNCTION PARAMETER SPECIFICATION
Setting
24
PID trait switch
25
PID give switch 1
26
PID give switch 2
27
PID give switch 3
28
PID feedback switch 1
29
PID feedback switch 2
30
PID feedback switch 3
31
PLC pause
32
PLC restart
33
Swing frequency input
34
Swing frequency pause
35
Swing frequency reset
36
Frequency channel switch terminal 1
37
Frequency channel switch terminal 2
38
Frequency channel switch terminal 3
39
Frequency channel switch terminal 4
40
Timer touch terminal
41
Timer clear terminal
42
Counter clock input terminal
43
Counter clear terminal
44
DC brake order
45
Pre-excitation order terminal
46
Reserved
47
Reserved