AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
2:0.00-20.00mA
3: FM frequency pulse output
Specify AO1, AO2 terminal output signal types, selectable output voltage, output current; AO2 can be used as pulse
output.
Tip: After selecting output mode, you also need to select switch on-off mode on the control panel; S1
designated AO1 output, S5 designated AO2 output, for specific choice of the way, please see the connection
terminals jumper Table 3-5; inverter factory software and hardware default is 0 ~ 10V output, if you need to
change, please press the actual output signal to change the hardware and software at the same time.
F3.22
A01 output selection
F3.23
A02 output selection
Used for setting inverter monitor value corresponding to multifunction terminal (AO1), (AO2) output signal.
(AO1) output signal is decided by "0"digit of [F3.21].
(AO2) output signal is decided by "00"digit of [F3.21].
Setting
Monitor value
0
Give frequency
Output
1
frequency
2
Output current
3
Input voltage
4
Output voltage
5
Machine speed
6
Reserved
7
Output torque
8
PID give
9
PID feedback
10
Output power
11
Bus voltage
12
VS input
13
AI input
14
AS input
Setting range: 0-17
Function
Corresponding to current
give frequency
Corresponding to current
output frequency
Corresponding to current
output current
Corresponding to current
input voltage
Corresponding to current
output voltage
Corresponding to current
machine speed
Reserved
Corresponding to current
output torque
Corresponding to current
PID give
Corresponding to current
PID feedback
Corresponding to current
output power
Corresponding to current
input voltage
Corresponding to current
VS input
Corresponding to current AI
input
Corresponding to current
AS input
FUNCTION PARAMETER SPECIFICATION
AO min output
Min output corresponding
to 0.00Hz
Min output corresponding
to 0.00Hz
Min output corresponding
to 0.00A
Min output corresponding
to 0V
Min output corresponding
to
Min output corresponding
to 0 speed
Reserved
Min output corresponding
to 0.00% torque
Min output corresponding
to 0.00% PID give
Min output corresponding
to 0.00% PID feedback
Min output corresponding
to 0 power
Min output corresponding
to 0V
Min output corresponding
to VS input lower limit
Min output corresponding
to AI input lower limit
Min output corresponding
to AS input lower limit
110
Factory default: 0
Factory default:1
AO max output
Max output corresponding to
max frequency
Max output corresponding to
max frequency
Max output corresponding to
2 times of rated current
Max output corresponding to
2 times of rated voltage
Max output corresponding to
2 times of rated voltage
Max output corresponding to
speed corresponding to max
frequency
Reserved
Max output corresponding to
200% torque
Max output corresponding to
200% PID give
Max output corresponding to
100% PID feedback
Max output corresponding to
rated output power
Max output corresponding to
2 times rated DC voltage2
Max output corresponding to
VS input upper limit
Max output corresponding to
AI input upper limit
Max output corresponding to
AS input upper limit