AC100 HIGH-PERFORMANCE VC INVERTER MANUAL
6: RS485 communication given
The settings of items 0 to 6 are consistent with frequency given main channel selection [F0.03].
F0.06
Auxiliary channel gain
It is used to magnify or reduce the main channel input signal, can adjust given frequency of main channel in proportion.
F0.07
Frequency give channels combinations mode
LED "0" digit: combination mode selection It is used to select the combination method of the main input channel and
the auxiliary input channel of the give frequency.
0: Main channel valid: Only main channel [F0.03] is valid, auxiliary channel [F0.05] is invalid.
1: Auxiliary channel valid: Only auxiliary channel [F0.05] is valid, main channel [F0.03] is invalid.
2: Main+auxiliary The sum of main channel [F0.03] add auxiliary channel [F0.05] is the output frequency of the
inverter.
3: Main-auxiliary: The result of main channel [F0.03] minus auxiliary channel [F0.05] is the output frequency of the
inverter.
4: MAX {main, auxiliary}: The bigger one of main channel [F0.03] and auxiliary channel [F0.05] is the output
frequency of the inverter.
5: MIN {main, auxiliary} The smaller one of main channel [F0.03] and auxiliary channel [F0.05] is the output frequency
of the inverter.
6: Main*auxiliary Given frequency of main channel [F0.03] multiply certain percent which is percent of given frequency
of auxiliary channel [F0.05] responding to max frequency [F0.09]. The result is output frequency of the frequency
inverter.
LED "00" digit: frequency control direction selection It is used to select whether permit negative frequency change
the running direction of the frequency inverter when the result is negative.
0: invalid If result is negative, frequency inverter output 0.00Hz.
1: valid If result is negative, frequency inverter change running direction and output related frequency.
LED "000" digit: reserved
LED "0000" digit::reserved
Note: 1. When main*auxiliary, frequency only count positive value. When any channel frequency is negative,
count as 0.00Hz, frequency inverter output 0.00Hz.
2. Can't overlay main+auxiliary when JOG and multi step speed running.
3. When rotate direction selection [F0.16] is set as REV forbid, whatever frequency control direction
selection is set, frequency inverter outputs 0.00Hz frequency if count result is negative.
Tip: Given frequency synthesized by main channel and auxiliary channel also limited by upper limit frequency
and lower limit frequency.
Keyboard number set
F0.08
frequency
When frequency given channel is keyboard numbers, it is used to set and modify frequency. If [F4.04] LED "0" digit is 1,
the up/down key can modify the parameter value. Whether saving the modified value or not after power off is decided
by [F4.04] LED "00"digit
Setting range: 0.000-5.000
Setting range: 0000-0016