C.26

Pump starts (R41,470-R41,475)

The number of pump starts for the referenced pump relay.
This value comes from parameter Pump Starts (3.2.9.4.) (Page 260).
C.27

Parameter access (R43,998-R46,999)

Parameter values are given as integers in the range of registers from R44,000 to R44,999.
The last three numbers of the register correspond to the parameter number.
Parameter register #
44,000
44,001
44,002
...
44,999
Usually, the parameters are all read / write.
Note
• Parameters Write Protection (5.1.) (Page 271) and Master Reset (3.2.3.) (Page 254) are
Read only.
• Master Reset (3.2.3.) (Page 254) cannot be used via Modbus.
• See Data types (Page 339) for a description of the types associated with different
parameters.
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See Format words (Page 337).
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Format register #
46,000
46,001
46002
...
46,999
Communications
C.26 Pump starts (R41,470-R41,475)
Parameter
Write Protection (5.1.)
(Page 271)
Sensor Mode (2.1.3.)
(Page 163)
Material (2.1.6.) (Page 165)
...
Master Reset (3.2.3.)
(Page 254)