Scan Time (2.1.15.); Shot Delay (2.1.16.); Shot/Pulse Mode (2.1.17.) - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Parameter reference
8.6 Setup (2.)
8.6.1.15

Scan time (2.1.15.)

Shows the elapsed time, in seconds, since the point displayed was last scanned.
Index
Values
Related
This may be viewed as an Auxiliary Reading in the RUN mode.
8.6.1.16

Shot delay (2.1.16.)

Adjusts the delay (in seconds) between transducer shots.
Index
Values
Use this if transient acoustic noise within the vessel is causing measurement difficulties due
to echoes from one shot being received on the next. If more than one ultrasonic unit is
installed for redundancy, this value should be 0.
8.6.1.17

Shot/pulse mode (2.1.17.)

Determines what type of ultrasonic shots are fired.
Index
Options
Related
Increases the device's response when the monitored surface is close to the transducer face.
Select Short and long to have short and long acoustic shots fired for each measurement,
regardless of the transducer to surface distance. Select Short to have only short shots fired if
the Long confidence (3.2.11.2.) (Page 262) produced by a short shot exceeds the short Long
echo threshold (2.11.2.3.) (Page 223) and the monitored surface is always within the Short
shot range (2.11.2.12.) (Page 226).
168
Level
Range: 0.000 ... 9999 (Read only)
Sensor mode (2.1.3.) (Page 163)
Transducer
Range: 0.1 ... 4.0
Preset: 0.5
Single-point model
Global
Short
*Short and long
Empty (2.2.4.) (Page 170)
Long confidence (3.2.11.2.) (Page 262)
Long echo threshold (2.11.2.3.) (Page 223)
Short shot range (2.11.2.12.) (Page 226)
Dual-point model
Transducer
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC