Display after Auto False Echo Suppression
Hover level (2.11.3.4.)
Defines (in percent) how high the TVT curve is placed above the profile, relative to the
largest echo. When the device is located in the center of the vessel, lower this parameter to
prevent multiple echo detections.
Values
Shaper mode (2.11.3.5.)
Turns the TVT Shaper ON or OFF.
Index
Options
Related
Turn the TVT Shaper ON before using TVT Shaper (2.11.4) (Page 231) and afterwards. Turn
the TVT Shaper ON and OFF while monitoring the effect to pick up the true echo.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
TVT curve (learned)
Material level
False echo
Range: 0 ... 100%
Preset: 33 %
Single-point model
Global
*OFF
ON
TVT Shaper (2.11.4.) (Page 231)
Parameter reference
Dual-point model
Transducer
8.6 Setup (2.)