Pump Control; Setting A Pump Down Group - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

7.9

Pump control

7.9.1

Setting a pump down group

Example: sewage wet well
Set a group of three pumps to pump down a wet well
Set the common parameters
Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the unit, set your test values to be the same as the sample
values.
Parameter
Sensor Mode (2.1.3.)
(Page 163)
Material (2.1.6.)
(Page 165)
Response Rate (2.3.4.)
(Page 174)
Transducer (2.1.5.)
(Page 164)
Units (2.1.1) (Page 162)
Empty (2.2.4.)
(Page 170)
Span (2.2.2.) (Page 169) Global
Example assumes a single measurement unit. If your device has dual-point software
1
installed, then some parameters are indexed by two level points.
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Inflow
Span (2.2.2) (Page 169)
Index
Global
Global
Global
Global
Global
Global
Empty (2.2.4.) (Page 170)
Outflow
Value/Mode
1
*Level (Page 163) Operation = *Level (Page 163)
Liquid
Medium
XPS-10
Meters
1.8
1.4
7.9 Pump control
Description
Material = *Liquid
Maximum Process Speed = *Medium
(1.0 m/min) (Page 174)
Transducer = XPS-10 (single-point
preset)
Units = Meters
Empty = 1.8 m
Span = 1.4 m
Operating
117