Fail-Safe Advance (2.4.6.); Ma Output Selector (2.4.7.); Ma Fail-Safe Mode (2.4.8.) - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

8.6.4.6

Fail-safe advance (2.4.6.)

Sets the speed the device advances to, and returns from, the Fail-safe Material Level.
Index
Options
Related
8.6.4.7

mA Output selector (2.4.7.)

Sets the mA Output index for all applicable parameters in this sub-menu
Options
8.6.4.8

mA Fail-safe mode (2.4.8.)

Use for fail-safe operation, independent of the Material Level (2.4.5.) (Page 178).
Index
Options
Related
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC
Level
*Restricted
Immediate
Fast back
Response rate (2.3.4.) (Page 174)
LOE timer (2.4.2.) (Page 177)
Material level (2.4.5.) (Page 178)
Fill rate/minute (2.3.2.) (Page 173)
Empty rate/minute (2.3.3.) (Page 173)
*mA Output 1
mA Output 2
mA Output
*OFF
mA output responds to Material level (2.4.5.) (Page 178).
HI
Produce the Span mA output immediately.
LO
Produce the Empty mA output immediately.
Hold
Last known value is held until normal operation resumes.
Value
mA output goes to user-selected value defined in mA Fail-safe
Value (2.4.9.) (Page 180)
Current output function (2.5.3.) (Page 181)
Advances to/from Fail-safe Material Level as set by
Response Rate (2.3.4.) (Page 174)
Fill rate/minute (2.3.2.) (Page 173)
Empty rate/minute (2.3.3.) (Page 173)
Fail-safe Material Level assumed right away.
Fail-safe Level Advance is restricted, return is immedi-
ate.
Parameter reference
8.6 Setup (2.)
.
179